I. Overall Fire Protection System Design

1. System Composition

The system consists of pre-engineered, non-pressurized FK-5-1-12 (perfluorohexanone) fire suppression units, thermal aerosol fire suppression devices, audible and visual alarms, dual-function composite detectors, and a centralized data controller.

2. Equipment Deployment

(1) Battery Compartment

  • One BSP1000 composite detector installed at the top

  • One QRR0.15G/S-CFLC thermal aerosol fire suppression device installed at the top

(2) Electrical Compartment

  • One BSP1000 composite detector installed at the top

  • One YF0.5Q-CFLC FK-5-1-12 fire suppression device installed at the top

(3) PACK Compartment

  • One QRR0.144G/S-CFLC pulsed thermal aerosol fire suppression device installed in each PACK compartment

Energy Storage Power Station Fire Protection System Solution

3. Energy Storage Cabinet

  • One CNS89 audible and visual alarm installed

(1) Interlocking Logic and Detector Responsibilities

  • BSP1000-2 Detector No. 1 is dedicated to monitoring the electrical compartment.

  • BSP1000-2 Detector No. 2 is dedicated to monitoring the battery compartment.

  • Both detectors communicate continuously with the centralized data controller.

The data controller uploads real-time operational data to the BMS, including detector alarm status.

  • When the BSP1000 in the electrical compartment reaches a Level 2 alarm, the audible and visual alarm is activated; when it reaches a Level 3 alarm, the YF0.5Q-CFLC FK-5-1-12 fire suppression device is activated.

  • When the BSP1000 in the battery compartment reaches a Level 2 alarm, the audible and visual alarm is activated; when it reaches a Level 3 alarm, the QRR0.15G/S-CFLC thermal aerosol fire suppression device is activated.

Each PACK module may be equipped with a QRR0.144G/S-CFLC device, which uses temperature-sensing automatic activation. When the temperature reaches 170 °C ±10 °C, the device activates automatically. After activation, the feedback component reports the activation status.

FK-5112 Fire Suppression System

(2) Fire Suppression System Performance Requirements

Protection Configuration:

  • PACK compartment: Pulsed thermal aerosol fire suppression device (QRR0.144G/S-CFLC)

  • Battery compartment: Thermal aerosol fire suppression device (QRR0.15G/S-CFLC)

  • Electrical compartment: FK-5-1-12 fire suppression device (YF0.5Q-CFLC)

Alarm and Control Logic

  • Level 1 Early Warning:
    Smoke ≥ 0.55 dB/m
    Internal sampling frequency reduced from 12 s to 6 s

  • Level 2 Early Warning:
    Temperature ≥ 75 °C
    Audible and visual alarm activated; fire protection power-off signal sent to the BMS via the data controller

  • Level 3 Alarm:
    Smoke ≥ 1.0 dB/m and Temperature ≥ 75 °C
    24 V electrical signal output to activate the fire suppression device

Cable Requirements:

  • Power supply cables: RVVSP 2 × 1.5 mm² flame-retardant cables

  • Communication cables: RVVSP 2 × 2 × 1.5 mm² twisted, shielded, flame-retardant / fire-resistant cables

FK-5112 Fire Suppression System

4. Key Product Parameters

(1) FK-5-1-12 Fire Suppression Device for Electrical Compartment (YF0.5Q-CFLC)

  • Dimensions: 340 × 60 × 60 mm

  • Agent charge: 0.5 kg

  • Discharge time: ≤ 10 s

  • Activation conditions: Current ≥ 700 mA or temperature 180 °C ±10 °C

  • Operating temperature: 40–70 °C

(2) Pulsed Thermal Aerosol Fire Suppression Device for PACK Compartment (QRR0.144G/S-CFLC)

  • Dimensions: 155 × 104 × 16 mm

  • Net weight: 380 ±30 g

  • Protected volume: 1.5 m³

  • Service life: 10 years

  • Activation modes: Thermal activation (170 °C ±10 °C) or electrical activation

  • Discharge time: ≤ 10 s

(3) Thermal Aerosol Fire Suppression Device for Battery Compartment (QRR0.15G/S-CFLC)

  • Dimensions: 255 × 66 × 46 mm

  • Fire suppression density: 100 g/m³

  • Protected volume: 1.5 m³

  • Service life: 10 years

  • Activation modes: Thermal or electrical activation (current ≥ 700 mA or temperature ≥ 170 °C)

  • Discharge time: ≤ 20 s

(4) Composite Detector (BSP1000)

  • Functions: Real-time monitoring of fire hazards in lithium battery enclosures

  • Power supply: DC 9–30 V

  • Features: Flexible installation

(5) Audible and Visual Alarm (CNS89)

  • Power supply: DC 24 V

  • Sound pressure level: 75–115 dB

  • Dimensions: 134 × 114 × 50 mm

(6) Centralized Data Controller

  • Functions: Receives data from detectors and the BMS; controls and interlocks audible and visual alarms and other devices

  • Communication interfaces: RS485 / CAN

  • Operating voltage: DC 24 V (wide range 9–30 V)

  • Operating temperature: –20 to +85 °C